Example for selecting a 1746 power supply, Chassis 1 contains: chassis 2 contains – Rockwell Automation 1747-ACNR15 ControlNet Adapter Module User Manual User Manual

Page 95

Advertising
background image

Publication 1747-UM003A-EN-P

Understanding Your SLC 500/1746 Control System B-3

Example for Selecting a 1746 Power Supply

Select a power supply for chassis 1 and chassis 2 for the control system below.
(The worksheets for this example start on Page B-4.)

Chassis 1 Contains:

Chassis 2 Contains:

?

?

PC

1747-AIC

DH-485 Network

Chassis 1

Chassis 2

Slot Slot

0 1 2

3

0 1 2 3 4 5

6

Table B.1 Chassis 1

Slot
Number

Description

Catalog Number

Power
Supply at 5V
dc (Amps)

Power Supply at
24V dc (Amps)

0

Processor Unit

1747-L524

0.35

0.105

1

ControlNet Scanner

1747-SCNR

0.90

Not Applicable

2

Transistor Output
Module

1746-OB8

0.135

Not Applicable

3

Triac Output Module

1746-OA16

0.37

Not Applicable

Peripheral
device

Isolated Link Coupler

1747-AIC

Not
Applicable

0.085

Total Current:

1.755

0.190

(1)

(1) Power Supply 1746-P1 is sufficient for Chassis #1. The “Internal Current Capacity” for this power supply is 2 Amps at 5V

dc, 0.46 Amps at 24V dc.

Table B.2 Chassis 2

Slot
Number

Description

Catalog Number

Power
Supply at 5V
dc (Amps)

Power Supply at
24V dc (Amps)

0

ControlNet Adapter

1747-ACNR15

0.900

Not Applicable

1

Input Module

1746-IA16

0.085

Not Applicable

2

Input Module

1746-IA16

0.085

Not Applicable

3

Relay Output Modules

1746-OB32

0.452

Not Applicable

4

Relay Output Modules

1746-OB32

0.452

Not Applicable

5

Relay Output Modules

1746-OB32

0.452

Not Applicable

6

Combination Module

1746-IO12

0.09

0.07

Total Current:

2.616

0.07

(1)

(1) Power Supply 1746-P2 is sufficient for Chassis #2. The “Internal Current Capacity” for this power supply is 5 Amps at 5V dc,

0.96 Amps at 24V dc.

Advertising