2-2 Installing Your ControlNet Adapter Module

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by
applying the safety requirements of EN 61131-2 Programmable Controllers,
Part 2 - Equipment Requirements and Tests.

For specific information required by EN 61131-2, see the appropriate sections
in this publication, as well as the following Allen-Bradley publications:

Industrial Automation Wiring and Grounding Guidelines For Noise
Immunity
, publication 1770-4.1

Automation Systems Catalog, publication B111

Determining Power
Requirements

The ControlNet adapter module requires a maximum backplane current of
900 mA at 5V dc. Remember to add this amount to other current
requirements for your I/O chassis.

Setting the Network
Address Switches

The switches on the top of the adapter module determine the network address
of the adapter. The two switches are:

the ten’s switch

the one’s switch

The combination of these switches allows selection of network addresses from
01 to 99.

Figure 2.1 Setting the Network Address

NOTE

00 is an invalid number.