Power supply specifications – Rockwell Automation 1747-ACNR15 ControlNet Adapter Module User Manual User Manual

Page 94

Advertising
background image

Publication 1747-UM003A-EN-P

B-2 Understanding Your SLC 500/1746 Control System

Power Supply Specifications

Description:

Specification: 1746-

P1

P2

P3

P4

P5

P6

P7

Line Voltage

85 to 132/170 to 265V ac 47
to 63 Hz

19.2 to 28.8V
dc

85 to 130/170
to 265V ac 47
to 63 Hz

90 to 146V dc 30 to 60V

dc

10 to 30V dc

Typical Line
Power Reqmnt.

135 VA

180 VA

90 VA

240 VA

85 VA

100 VA

12V dc input:
50 VA

24V dc input:
75 VA

Maximum
Inrush Current

20A

45A

20A

20A (required for turn-on)

Internal
Current
Capacity

2A at 5V dc
0.46A at 24V
dc

5A at 5V dc
0.96A at 24V
dc

3.6A at 5V dc
0.87A at 24V
dc

10.0A at 5V dc
2.88A at 24V
dc

(1)

5A at 5V dc
0.96A at 24V dc

12V dc input:
2.0A at 5V dc
0.46A at 24V
dc

24V dc input:
3.6A at 5V dc
0.87A at 24V
dc

Fuse
Protection

(2)

1746-F1 or
equivalent

(3)

1746-F2 or
equivalent

(4)

1746-F3 or
equivalent

(5)

Fuse is soldered in place.

24V dc User
Power Current
Capacity

200 mA

Not
Applicable

1A

(1)

200mA

Not Applicable

24V dc User
Power Volt.
Range

18 to 30V dc

20.4 to 27.6V
dc

18 to 30V dc

Ambient
Operating
Temperature

0

°

C to +60

°

C (+32

°

F to +140

°

F)

Current capacity is derated 5% above +55

°

C.

0

°

C to +60

°

C

(+32

°

F to

+140

°

F) no

derating

0

°

C to +60

°

C (+32

°

F to +140

°

F)

Current capacity is derated 5% above +55

°

C.

Isolation

(6)

1800V ac RMS for 1s

None

(7)

2600V dc for
1s

1800V ac RMS for 1s

600V ac RMS for 1s

CPU Hold-up
Time

(8)

20 ms (full load) 3000 ms (no
load)

5 ms (full
load)
1000 ms (no
load)

20 ms (full
load)
3000 ms (no
load)

20 ms (full
load)
3000 ms (no
load)

5 ms (full
load)
1500 ms
(no load)

12V dc input:
1.37 ms at 0V
dc (full load)
895 ms at 0V
dc (no load)
10 ms at 9V
dc (full load)
continuous at
9V dc (no
load)

24V dc input:
40 ms at 0V dc
(full load)
1860 ms at 0V
dc (no load)
790 ms at 11V
dc (full load)
continuous at
11V dc (no
load)

Certification

UL listed
C-UL or CSA certified (as indicated by product or packaging markings)
CE compliant for all applicable directives

Hazardous
Environment
Certification

Class I, Division 2

(1) The combination of all output power (5 volt backplane, 24 volt backplane, and 24 volt user source) cannot exceed 70 watts.
(2) Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the

power line.

(3) Equivalent fuses: 250V-3A fuse, Nagasawa ULCS-61ML-3, or BUSSMAN AGC 3.
(4) Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3.
(5) Equivalent fuse: 125V-3A fuse, Nagasawa ULCS-61ML-5, or BUSSMAN AGC 5.
(6) Isolation is between input terminals and backplane.
(7) No isolation between input terminals and backplane. However, dielectric withstand between input terminals and chassis ground terminal is 600V ac RMS for 1s.
(8) CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.