Health Indicators and Display Mnemonics

OK LED

Display

Description

Probable Cause

Recommended Action

Off

None

Module is not communicating.

Power supply fault.

Check power supply, and seat
adapter firmly in chassis.

None

Module is not communicating.

Defective adapter.

Contact Allen-Bradley service.

POST

Adapter is running Power On Self
Test.

None

None

Amber

0000
through
9999

Adapter is running Power On Self
Test.

None

None

A/A

Adapter is displaying Series and
Revision level.

None

None

INIT

Adapter is loading and
initializing operating system.

None

Adapter requires ControlNet
configuration.

Solid Red

FATL
Number
Number

Module is not communicating.

The Adapter has either failed a
hardware test, or gone into a
state from which it cannot
recover. The numbers following
the FATL describe the problem in
detail.

Document the numbers. Power
cycle the adapter. Contact
Allen-Bradley service.

Flashing
Red

A#00 ERR

Module is not communicating.

The node address switches are
set to 00 which is not valid.

Power the adapter off, remove
the adapter from the chassis,
change the node address switch
to something other than 00,
replace the adapter in the
chassis, and apply power.

DUP NODE

Module is not communicating.

The adapter has detected a
duplicated node address on the
network.

Correct the duplicate node
address problem.

Flashing
Green

IDLE

NET ERR

Module is not communicating.

The adapter has detected a cable
fault and is attempting to
recover. The adapter is sending
the three “NET ERR” packets.

None, check cable if problem
persists.

Solid Green

ACTV A#XX

Module is working properly.

None

None

BOOT
A#XX

Module is on network, but not
supporting any connections.

The main code in the module has
failed, or the main code is being
updated.

Update the main code with the
latest Series and Revision code.

CODE
UPDT

Firmware update mode.

Adapter firmware is being
updated via ControlFlash update
utility.

None

Advertising