Rockwell Automation 1747-ACNR15 ControlNet Adapter Module User Manual User Manual

Page 131

Advertising
background image

Publication 1747-UM003A-EN-P

Understanding Your SLC 500/1746 Control System B-39

Heat Dissipation Calculation Example

If your controller consists of the following hardware components, calculate
heat dissipation as shown in the worksheet on Page B-41.

The following table details the total watts dissipated by the modules and
peripheral devices in the above SLC 500 controller.

DTAM

Chassis 1

Chassis 2

Peripheral Device

Slot

0

1

2

3

Slot

1

2

3

3

User Power to Peripheral

Table B.10 Watt Dissipation

Chassis 1

Chassis 2

Slot Number

Catalog
Number

Min. Watts

Max. Watts

Slot Number

Catalog
Number

Min. Watts

Max. Watts

0

1747-L511

1.75

1.75

4

1746-IA16

.425

4.8

1

1746-BAS

3.75

3.8

5

1746-IA16

.425

4.8

2

1746-IA8

.250

2.4

6

1746-OW16

5.17

5.5

(2)

3

1746-OV8

.675

6.9

7

1746-OW16

5.17

5.7

Peripheral
Device

1747-DTAM

2.5

2.5

Not
Applicable

Not
Applicable

Not
Applicable

Not
Applicable

User Power to
Peripheral

Not
Applicable

Not
Applicable

Not
Applicable

Not
Applicable

Not
Applicable

2.4

(1)

Not
Applicable

(1) The user power on the 1746-P1 power supply for Chassis 2 is being used to power a peripheral (100 mA at 24V dc).
(2) This output card uses 5.5 watts because only 10 points are on at any one time. Using the calculated watts formula - (number of p oints energized x watts per point) +

minimum watts = heat dissipation of module - the calculated watts for the 1746-OW16 module is 5.5W: (10 points X.033) + 5.17 = 5.5W.

Advertising