Publication 1747-UM655B-EN-P - June 2007

130 1747-SDN Module Firmware History

If a slave in the scanlist does not match the identity of the slave
at that address on the network, the module does not
communicate with that slave again. After the mismatch is
resolved, you have to cycle power to the module to reestablish
communication.

If you have not experienced any of these anomalies and want to flash
upgrade this module to firmware revision 7.006, please contact
Rockwell Automation Technical Support at 440-646-3223.

Revision 6.002

This section describes the enhancements and corrected anomalies for
firmware revision 6.002.

Electronic Data Sheet Requirement

The 6.002 firmware revision of the module requires the latest EDS file
for RSNetWorx for DeviceNet software. If the software displays the
device as an unknown device, then you must download the latest EDS
file.

You can get the latest EDS file online at:

http://www.ab.com/networks/eds.

Follow these steps once you are at this location.

1. Click DeviceNet.

2. Enter the catalog number: 1747-SDN.

3. Enter Major Revision: 6.

4. Enter the Minor Revision: 2.

5. Click Search.