Publication 1747-UM655B-EN-P - June 2007

20 Before You Begin

the size of the input data/output data.

exactly where to map the input or output data for your
processor to read or write.

how your processor reads each device’s input data (M1/M0 file
or discrete I/O).

RSNetWorx Software as a
Configuration Tool

RSNetWorx for DeviceNet software is used to configure the 1747-SDN
module’s data tables. This software tool connects to the 1747-SDN
module over the DeviceNet network via a computer RS-232 interface
(1770-KFD module) or PC Card (1784-PCD, 1784-PCID, or
1784-PCIDS).

The configuration dialog map below shows the RSNetWorx for
DeviceNet dialogs used to configure the 1747-SDN module and the
navigation paths between them.

The use of these dialogs is described in Chapter 4.

Data Table Information

User-configured Tables

Data in This Table

RSNetWorx Software Configuration
Dialog

SCT

Basic operation parameters

I/O communication data
(enable/disable)

Interscan delay

Background poll ratio

1747-SDN module configuration

SLT

Device-specific identification data

Scanlist editor (SLE)

Data transfer method

Transmit/receive data size

Edit device I/O parameters

Input and output data source and
destination locations

These values can be configured
automatically through the AutoMap
function or manually through the Data Table
Map

TIP

RSNetWorx for DeviceNet software can also communicate with
the 1747-SDN module via an Ethernet or Data Highway Plus
network.

See Chapter 5.