Publication 1747-UM655B-EN-P - June 2007

82 Creating and Running the Example Application Program

Download and Run the
Program

You cannot go online to the processor directly over the DeviceNet
network. The following sections provide examples of downloading
and running the program by using these networks:

ControlNet

Ethernet

Data Highway Plus

Download and Run the Program via a ControlNet Network

Follow these steps to download and run the example program via a
ControlNet network.

1. From the RSLogix 500 Communication menu, choose System

Comms.

The Communication dialog appears. Your dialog may look
different depending upon the drivers and other devices you
have installed.

2. Click the + next to your ControlNet driver (AB_KTC-1) to

expand the tree.

3. Select the 1747-KFC15 module as shown above and click

Download.

Your program is downloaded to the controller.