SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 11

Publication 1747-IN019G-EN-P - December 2011

17.

Click OK.

18.

You may need to wait several seconds before the Progress dialog box appears.
A typical sequence is shown below. While the download is in progress, the ENET LED changes
from a solid green to flashing green to solid red and then turns solid green again. When the
daughtercard update is complete, the ENET LED flashes green. The download process of the
daughtercard firmware can take up to approximately two minutes.

19.

When the message ‘Waiting while module burns flash…’ and all progress bars are displayed, check
the AB_SNMP dialog box. Open it from your taskbar if it does not appear automatically.

The AB_SNMP dialog box prompts you to turn off power, remove the processor, move the jumper
to Program, re-insert the processor, and apply power.

20.

Wait for the ENET LED to turn solid green.

ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is
removed from the SLC 500 power supply