Target module not in proper state for programming, Failed to receive initial tftp request from target – Rockwell Automation 1747-DU501 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Installation User Manual

Page 17

Advertising
background image

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 17

Publication 1747-IN019G-EN-P - December 2011

power down the processor and check the J4 jumper position.

3.

Restart the firmware upgrade procedure in the Use ControlFLASH section.

Target Module Not in Proper State for Programming

The following dialog box appears when this error occurs:

To clear this error:

1.

Place the SLC 5/05 processor into PROG mode.

2.

Ensure that DHCP is not selected.

3.

Restart the firmware upgrade process at the beginning of the Use ControlFLASH section. If the
error occurs again, power-cycle the SLC 5/05 processor and restart the firmware upgrade process.

Failed to Receive Initial TFTP Request from Target

The following dialog boxes appear in the sequence shown when this error occurs.

To clear this error:

1.

Connect the processor’s Ethernet port directly to the PC Ethernet port using a crossover cable, or
disable or uninstall any firewall VPN or virus protection software running on the PC.

2.

Power-cycle the processor.

3.

Restart the firmware upgrade process.

ATTENTION: Do not remove the processor from the SLC 500 chassis until all
power is removed from the SLC 500 power supply.