Use controlflash – Rockwell Automation 1747-DU501 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Installation User Manual

Page 5

Advertising
background image

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 5

Publication 1747-IN019G-EN-P - December 2011

This returns the processor to the initial factory conditions.

Use ControlFLASH

1.

Launch the ControlFLASH application under Programs>Flash Programming Tools.

2.

Verify that the J4 jumper of the SLC 5/05 processor being upgraded is set to Protect.

The daughtercard firmware can only be updated when the J4 jumper is set to Protect.

ATTENTION: Do not interrupt the flash procedure. Once you have begun to download the
firmware for either the daughtercard (step 18) or the motherboard (step 24), the SLC 5/05 is
put into an unrecoverable state if you lose power or communications for any reason.

GND VBB

SLC 500

CAT

SER

SERIAL NO.

PROC. REV.

)

UL

)

SA

PROCESSOR UNIT

MADE IN USA

LISTED IND. CONT. EQ.

FOR HAZ. LOC. A196

CLASS 1, GROUPS A, B, C AND D, DIV. 2

FAC

OPERATING TEMPERATURE CODE T3C

1

3

PROTECT

PROGRAM

J4

OS #

SER

FRN

OPERATING SYSTEM INFO

PLACE FRN UPGRADE LABEL HERE

WHITE

RED

+
-

BATTERY

CURRENT REQUIREMENTS: 1A @ 5 VDC

200mA @ 24 VDC