After Successfully Updating Your SLC 5/05 Processor

1.

Remove power from the SLC 500 power supply and remove the processor from the chassis.

2.

Apply the enclosed operating system upgrade label to the SLC 5/05 processor nameplate.

3.

Re-insert the processor into the chassis and apply power.

4.

Restore your program to the processor.

ControlFLASH Error Messages

There are three error messages you can receive.

Invalid Catalog Number

Target Module Not in Proper State for Programming

Failed to Receive Initial TFTP Request from Target

Invalid Catalog Number

The following error message is displayed if:

the ControlFLASH tool is unable to match the processor to the catalog number that was selected in
the catalog Number dialog box, or

the tool is unable to identify the processor type selected because the J4 jumper is in the Program
position.

To clear this error:

1.

Click OK.

2.

Click Cancel to go to the Catalog Number dialog box. You may either:

select the correct catalog number in the dialog box, and proceed with the update, or

ATTENTION: Do not remove the processor from the SLC 500 chassis until all
power is removed from the SLC 500 power supply.