8 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

Publication 1747-IN019G-EN-P - December 2011

10.

Click the Get Info button.
If the IP address was previously configured in the processor, go to step 12.
The AB_SNMP – BOOTP Server dialog box appears, indicating that this IP address has not been
configured into the processor.

11.

Enter the hardware address of the SLC 5/05 processor that is being upgraded and click OK. The
hardware address is noted in step 2 of the section, Prior to Running ControlFLASH, on page 3.

The AB_SNMP – BOOTP Server Running dialog box may take several seconds or
minutes to appear.

You may need to wait several seconds or minutes before you are returned to the AB_SNMP.DLL –
Enter IP Address dialog box. Within a few seconds, the Device Identification box displays the
processor’s current revision information.