Installing the 1779-KP3

Communication Interface

Chapter 2

2Ć4

Table 2.B

Group 2 Switch Settings

If:

Set

switch

number:

To:

you want the KP3 to accept write commands to the program

areas of the PLC-3 memory, regardless of the PLC-3

keyswitch position

4

ON

you want the PLC-3 keyswitch position checked to

determine if write commands are allowed to the program

areas of PLC-3 memory

OFF

you want the KP3 to accept write commands to the data

table areas of the PLC-3 memory, regardless of the PLC-3

keyswitch position

5

ON

the PLC-3 keyswitch position checked to determine if write

commands are allowed to the data table areas of PLC-3

memory

OFF

you want the KP3 to accept write commands to the status

areas of memory, regardless of the PLC-3 keyswitch

position

6

ON

you want the PLC-3 keyswitch position checked to

determine if write commands are allowed to the status areas

of PLC-3 memory

OFF

Important: Do not touch switches 1, 2, and 3; they are reserved for future use.

The MAC Board Switch Your Module May Have

If your 1779–KP3 Interface has a series A MAC board, you will also have
a 2–switch group on the MAC board. You can view it from the top of the
module looking down at the MAC board. Figure 2.3 shows the location
of this switch in relation to the host board switches; this is a side view of
this group. Note that this switch does not exist on redundant modules
(1779–KP3R) or 1779–KP3 modules with series B MAC boards.

Figure 2.3

The MAC Board Switch Group

1 2 3 4 5 6 7 8

Host Board

Mac Board

Side view of 2-switch Group

1 2 3 4 5 6 7 8

Front of Module

11003-I