Appendix A

AĆ4

Table A.B

LEDs Associated with the MAC Board

When this LED(s):

is:

then:

IN-RING

ON green this node is a member of the logical ring on the Data Highway II

link.

SEEKING

ON yellow this node is trying to become a member of the logical ring, or

trying to build a logical ring in the case that a ring does not

already exist.

OFF

this node is not a member of a logical ring and is not seeking

membership

DUP ADDR

ON red

another node has the same address on the Data Highway II

link. This condition also places this node into the disconnect

state.

REDUN WARN

1

ON yellow a valid signal is being received at only one of the two Data

Highway II ports.

PORT READY

ON green the on-board relay connecting the MAC board to the dropline is

closed.

SIG QUAL

ON green a valid signal is being received at this Data Highway II port.

TAP FAIL

This LED is not used at this time, and will remain OFF.

EXT TAP CONFIG

This LED is not used at this time, and will remain OFF.

PORT READY

ON green the on-board relay connecting the MAC board to the dropline is

closed.

SIG QUAL

ON green valid data is being received on Data Highway II.

ON red

a difference in data was noted between this port and the other

port, and this port was found to be in error. Each detected error

causes this LED to be turned ON for one-half second.

OFF

no data is being received.

TAP FAIL

ON red

the extended tap has failed or its dropline connection to the port

has opened.

Important: this LED can only go ON if the switch on the MAC

board is set for extended tap

2

1

This LED is only on the redundant module 1779-KP3R.

2

Extended taps are not available with this product release. Although these indicators are present,

they do not perform the functions at this time.