Addressing techniques – Rockwell Automation 1779-KP3R DATA HIGHWAY II User Manual

Page 43

Advertising
background image

Programming

Chapter 3

3Ć8

Syntax for the TMOVE Command With an Integer Constant and the

NOSTATUS Qualifier

The syntax for the TMOVE command when using an integer constant
and the NOSTATUS
qualifier is:

TMOVE <integer constant> TO <address> NOSTATUS or
TMOVE TO <address> <integer constant> NOSTATUS

Where:

is:

TMOVE

the command that tells the KP3 to transfer data to or from a remote

node.

<integer constant>

what you use in place of the FROM qualifier. The correct format is

#digit, where digit is either 0 or 1.

TO

the qualifier that specifies the destination of the data transfer; you

can abbreviate as T. You must specify the TO qualifier and it must

be followed an address (which must include a data table address

and can include a remote node address).

<address>

the destination address for the data you are moving. This is either

a Data Highway II node address or programmable controller

memory address (see section titled Addressing Techniques for

addressing style information).

NOSTATUS

the qualifier used only with a TMOVE command designed to

transfer data to some remote node. Use when error reporting is not

necessary and you want to eliminate the time spent receiving

information about the success or failure of the command. You can

abbreviate as N.

These are examples of using the TMOVE command with an integer
constant:

TMOVE #1 TO :76$222/3
TM #0 T :76$B2:3/4

See the section titled Programming Examples, at the end of this chapter,
for more command examples.

In the previous sections, we used many examples with <address> as part
of the PLC–3 command line. This describes what type of information you
place into your command line to designate an address. There are two
types of addressing we cover:

Data Highway II node addresses
programmable controller memory addresses

Addressing Techniques