Rockwell Automation 1779-KP3R DATA HIGHWAY II User Manual

Page 25

Advertising
background image

Installing the 1779-KP3

Communication Interface

Chapter 2

2Ć9

The Message Time-outs Menu

When you choose option 1, you receive the Message Time-outs menu:

KP3 1, MESSAGE TIMEOUTS

1 TIME CRITICAL TIMEOUT

2 SUPERVISORY TIMEOUT

ENTER NEXT >

3 THIRD-PARTY TIMEOUT

This

option:

allows you to:

Minimum value: Maximum

Value:

Default

Value

1

:

1

set the time-out for

time-critical messages.

0.01 seconds

10.00 seconds

.50 seconds

2

set the time-out for

supervisory messages.

Use to send information

that in not time critical,

such as reports.

0.01 seconds

650.00 seconds

1.00 seconds

3

(Not available with this release.)

1

The default value appears the first time you use this menu.

Important: You must enter the time–out value for time–critical and
supervisory messages with a decimal point and two digits to the right of it.

The Token Hold Factor Menu

When you select option 2 from the Data Highway Interface menu, you
receive the Token Hold Factor menu:

KP3 1, TOKEN HOLD FACTOR

FACTOR = 1

ENTER FACTOR >

This menu allows you to set and display the amount of time a node is
allowed to possess the token before passing it to the next node. The menu
allows you to change the link–layer token hold factor.

You can enter a number from 1 to 256, the default factor is 1. With a
factor of 1, the node will hold the token for the standard hold time. The

Advertising