Rockwell Automation 1779-KP3R DATA HIGHWAY II User Manual

Page 42

Advertising
background image

Programming

Chapter 3

3Ć7

See the section titled Programming Examples, at the end of this chapter,
for more command examples.

Syntax for the TMOVE Command With the FROM and NOSTATUS Qualifiers

The syntax for the TMOVE command when using the FROM and
NOSTATUS
qualifiers is:

TMOVE FROM <address> TO <address> NOSTATUS or
TMOVE TO <address> FROM <address> NOSTATUS

Where:

is:

TMOVE

the command that tells the KP3 to transfer data to or from a remote

node.

FROM

the qualifier that specifies where you want to transfer data from;

you can abbreviate as F. FROM is always followed by an address

(which must include a data table address and can include a remote

node address).

<address>

the address where the data that you are moving resides. This is

either a Data Highway II node address or programmable controller

memory address (see section titled Addressing Techniques for

addressing style information).

TO

the qualifier that specifies the destination of the data transfer; you

can abbreviate as T. You must specify the TO qualifier and it must

be followed an address (which must include a data table address

and can include a remote node address).

<address>

the destination address for the data you are moving. This is either

a Data Highway II node address or programmable controller

memory address (see section titled Addressing Techniques for

addressing style information).

NOSTATUS

the qualifier used only with a TMOVE command designed to

transfer data to some remote node. Use when error reporting is not

necessary and you want to eliminate the time spent receiving

information about the success or failure of the command. You can

abbreviate as N.

These are examples of using the TMOVE command with the FROM and
NOSTATUS qualifiers:

TMOVE FROM :66$010 TO $B2:3 NOSTATUS
TM T $B2:3 F :66$010 N