Installing the 1779-KP3

Communication Interface

Chapter 2

2Ć12

Once you have installed and configured the KP3 module, follow the
procedure below to connect it to the highway.

Important: If you are connecting a backup PLC–3 system to Data
Highway II, remember that you must run at least 30 feet of trunkline cable
between droplines to the primary and backup KP3 modules.

1.

Locate the Data Highway II Port on the KP3 front panel.

EXT TAP CONFIG

1

1

L

I

N

K

A

D

D

R

E

S

S

M

S

D

DATA

HWY II

PORT

Dropline

connection to the

network.

KP3 Front Panel

2.

Connect a Data Highway II dropline to the connector by sliding the
dropline connector over the port and twisting the collar clockwise.

If you have a KP3R module, repeat steps 1 and 2 for the port labeled Data
Highway II PORT 2.

You can connect a PLC–3 to multiple Data Highway II links. The PLC–3
requires one KP3 for each Data Highway II link it communicates over.

Follow the procedure below to connect a PLC–3 to multiple Data
Highway II links.

1.

Install one KP3 in the PLC–3 chassis for each link the PLC–3 will
communicate over.

2.

Select a unique module number on the thumbwheel of each KP3 in
the same chassis.

3.

Connect each KP3 module to separate links via separate droplines.

Connecting the KP3 to Data

Highway II

Connecting a PLC-3 to

Multiple Data Highway II Links