Interpret the status indicators at startup – Rockwell Automation 2711C-xxxx PanelView Component HMI Terminals User Manual

Page 91

Advertising
background image

Publication 2711C-UM001I-EN-P - July 2014

91

Troubleshoot the System Chapter 6

POST errors are fatal and most likely due to failed hardware. A fatal error during
firmware installation and loading is most likely recoverable by installing the
appropriate firmware.

Interpret the Status Indicators at Startup

The C400 terminal has a Power indicator on the front of the unit to identify the
system status. The table shows system indicator status.

The C400, C600 and C1000 terminals have indicators on the back of the unit to
isolate operating problems.

• Comm indicator for communication
• Fault indicator for hardware faults

Firmware Image Validation (CRC/Format) Failure

Fatal

1E

Firmware Image Compatibility Failure

Fatal

1F

Firmware Write to Flash error

Fatal

A5

Firmware Read-After-Write Verify

Fatal

D2

Invalid or missing Firmware Image

Fatal

0A

Other Commonly Observed Status Codes

Message

State

Code

Boot Loader connects to PC via USB Device

AutoTest

0A

Boot Loader loads Firmware Image into RAM

AutoTest

E6

Boot Loader jumps to Operating System

AutoTest

FF

Operating System start up

Boot

G0

Operating System Initialize

Init

I1…J0

Application Registration and Initialize

Init

N1…N3

Application Load and Execute

Load

N4…N6

System Status LED Indicator

LED Indicator

Description

Green

System is running and display is switched on.

Red

System is running and display is in screen saver mode.

Firmware Installation and Loading

Message

State

Code

Advertising