6Ć3

Configuring Racks

6.1

Adding a Module to a Rack

The Add command on the Configure menu allows you to add

modules to a rack. See figures 6.2 and 6.3 for the screens displayed

when you are adding a module. Follow the procedure below to add a

module to the rack.

Figure 6.2 Ć Adding a Module, Part 1

Step 1.

Select an empty slot in the rack.

Step 2.

Select Add from the Configure menu. A list box with the

available modules will be displayed. The first column is a

two or three letter code for the module. The second

column is the model number of the module. The third

column displays the name of the module.

Step 3.

Select the module you want to add to the rack. The

modules listed below will require you to enter additional

information.
M/N 57C430A, M/N 57C431, M/N 57C435

AutoMax Processor Module

When you are adding a Processor module, you will be

prompted for the tick rate. The programmable tick rate"

allows you to change the definition of the tick. Changing

the tick, changes the time base for tasks. This change

allows you to run a task based on a unit of your choice.

The programmable tick rate can be set in increments of

0.5 msec. between 0.5 msec and 10.0 msec. For

compatibility with earlier Programming Executives, the

default tick rate is 5.5 msec. The tick rate is defined

separately for each Processor in a rack. The tick rate is

transferred when the configuration object code is

transferred to the Processor. The tick rate is set on the

Processor as soon as the configuration is loaded. See the