0 - on line menu: info/log, 1 info/log processor and udc information display, 0 on line menu: info/log – Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 171

Advertising
background image

13Ć1

On Line Menu: Info/Log

13.0 ON LINE MENU: INFO/LOG

Entering I" for Info/Log from the ON LINE menu allows you to

display information about the system software on any AutoMax

Processor or UDC module in the rack or to view the status and error

log, if any, for a selected task.

13.1

Info/Log Processor and UDC Information

Display

If you select Info/Log without having selected a task by using the

Enter key or <CR>, AutoMax will assume you want to display

information about an AutoMax Processor and the Common Memory

module (M/N 57C413B or 57C423) or a UDC module. You will be

prompted for the slot number of the AutoMax Processor or UDC

module of interest.

AutoMax Processor

Figure 13.1 shows a sample display for an AutoMax Processor in

slot 1 with no Common Memory module.

ON LINE direct

AUTOMAX

C: \LIB\SYS\RACK

EscăExit

Info/Log

Control Processor Information for Slot 1

Software ID:

422526Ć001C STD

Clock Tick (micro sec):

5500

CPU Utilization:

34%

Memory

Memory

Largest

Used

Free

Free Block

Battery

PROCESSOR 2924

151280

151280

Replace

COMMON

N/A

N/A

N/A

N/A

Figure 13.1 Ć Info/Log Processor Information Display

Advertising