AutoMax Processor Overview

10.4

Battery BackĆUp

The contents of AutoMax Processor RAM (read/write memory) are

preserved through power failures by the onĆboard battery backĆup.

As long as the LED labeled BAT. OK" on the front of the Processor

module is on, the battery is functional and 115 VAC is available to the

power supply in the rack. Should the system lose power, the

onĆboard battery can supply power to the Processor module for a

minimum of 42 days. Note that the battery backup is designed to

maintain the contents of RAM only. It is not a source of

unĆinterruptible power.
If you expect power to be off for long intervals during initial startĆup

and debugging, you should disconnect the battery backup on the

Processor module and make use of the superĆcapacitor also on

board each Processor module. Typically, the superĆcapacitor is

capable of retaining memory for 10 hours at a time with no battery

present. This procedure will avoid draining the Processor's battery

backĆup.
Reserved Battery Status Variables
Five preĆassigned variables are available for use in all application

tasks to test the status of the onĆboard battery of AutoMax Processor

and Common Memory modules. These common boolean variables

will have the value 1 if the battery is functional and 0 if the battery is

not functional. The variables are named according to the Processor

whose battery is being tested. BATTERYSTATUS0@ is used for the

Processor or Common Memory module in slot 0.

BATTERYSTATUS1@ is used for the Processor in slot 1, etc. up to

slot 4.

10.5

Module Watchdog Circuity

Each Processor module has a local watchdog timer which must be

reset by the operating system within a specified interval or the

Processor will execute a STOP ALL and all I/O modules in the local

rack will be reset (initialized to 0, FALSE, or OFF). The I/O modules in

the rack will also be reset if you remove a Processor module from a

singleĆProcessor configuration. All UDC tasks in the rack will also be

stopped, and most UDC registers will be reset. See 10.12 for more

information.
In a multiĆProcessor configuration, there is a system watchdog timer

located on the Common Memory module in slot 0 in addition to the

watchdog on each individual Processor module. If the system

watchdog is allowed to expire, the Common Memory module will

generate an interrupt, and one of the Processors in the rack will issue

a STOP ALL and reset the I/O modules in the rack. All Processor

modules in the rack will then shut down.
Each UDC module also has a local watchdog timer. If the watchdog

timer on a UDC module expires, the UDC module will generate an

interrupt, and one of the Processors in the rack will issue a STOP

ALL.