2 info/log task information display – Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 173

Advertising
background image

13Ć3

On Line Menu: Info/Log

The Software ID" depends on the software (operating system) and

hardware version of the UDC module. Tick Rate" refers to the speed

of the realĆtime clock in the UDC module. The Parameter File

Date/Time" will display the most recent date and time that the

parameter object file was generated. UDC Utilization" shows the

percentage of the UDC CPU's resources being used to run UDC

tasks. The UDC Utilization percentage is measured over a two

second time window. This value should be kept under 75% to ensure

that there are no overlaps in UDC task execution. Memory statistics

displayed for the UDC module are given in bytes.
The PMI OS Status" fields show whether the PMI operating system

has been loaded to each of the PMI Processors (Not Loaded or the

OS type (e.g., SA3000) ). If the PMI Processor is not connected to the

UDC module, this field will display Not Connected". The PMI

Parameters" fields show whether the drive parameters have been

loaded to each of the PMI Processors (Installed or Not Installed). If

the PMI OS Status field is displaying Not Connected", the PMI

Parameters fields will be blank. If the PMI Processor is connected to

the UDC module, the modules contained in the PMI rack(s) will be

listed.

13.2

Info/Log Task Information Display

If you select a task using the Enter or <CR> before selecting

Info/Log, AutoMax will display the task status and the error log, if any,

for the AutoMax or UDC task. A sample display is shown in figure

13.3.

ON LINE direct

AUTOMAX

C: \LIB\SYS\RACK

Info/Log

SLOT

NAME

TYPE

PRI

STATUS

5

APP1B

Blk

B

Stop

NUMBER

STATEMENT

DATE

TIME

ERROR SPECIFIC

EscăExit

F1ăHelp

ERROR LOG

SOURCE DATE

08Ć31Ć1993 02:08:18p

49ă = ă31 HEX

0

No date

00:00

0 =

0 HEX

774 = 306 HEX

0

No date

00:00

0 =

0 HEX

Precision lost in integer control variable to real conversion

775 = 307 HEX

0

No date

00:00

0 =

0 HEX

Real to integer overflow in FOR statement TO value

Error 31:

Slot=0

Bit=0 (Reg based on type of card in slot)

Net: drop=0,ą reg=0

Remote I/O:drop=0,

slot=0,

reg=0

Modbus: reg=n/a AutoMate: reg=n/a AĆB: file= n/a, reg=n/a Local I/O: reg=0

Figure 13.3 Ć Info/Log Task Information Display

Advertising