B - processor module error and status codes, Appendix b, Processor module error and status codes – Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 231

Advertising
background image

BĆ1

Processor Module Error and Status Codes

Appendix B

Processor Module Error

and Status Codes

All AutoMax Processor module error and status codes (displayed on the two

sevenĆsegment LEDs on the faceplate) are listed below, organized first by error

type and second, in numerical/alphabetical order.

Processor Overload

00

CPU overload

Corrective action: move one or more application tasks to other Processor

modules in the rack, or make scan times longer.

PowerĆUp Diagnostics

The following error codes are displayed while the Processor module performs

powerĆup diagnostics.
0.0.

EPROM failed

0.1.Ć 0.3.

Bad CPU

0.4.

Internal bus error test failure

0.5.

Parity test failure

0.6.

External bus error test failure

0.7.

Processor in the wrong slot

1.0. Ć 1.6.

RAM failure

2.0.

I/O protection failure

2.1.

PIO failed

2.2.

PC accelerator failed

2.3.

8253 timer/counter failed

2.4.

SIO failure

2.5.

Communications interrupt failed

2.6.

SIO interrupt failed

2.7.

8253 counter/timer interrupt failed

2.8.

Local watchdog failed

3.0.

Bad backplane

3.1.

Multibus parity test failure

4.0. Ć 4.5.

Common memory RAM failure

4.6.

Common memory system watchdog failure

5.0.

Processors with incompatible EPROMs in the rack.

Corrective action: replace the Processor, or replace the Common Memory

module if error codes 4.0.Ć 4.6. remain on.

Run Time Errors

02

Task or Configuration checksum failure

Corrective action: clear the error in the error log. This will also clear the LEDs.

Reload the parameter files and application tasks to the UDC module in the slot

referenced in the error log.

Advertising