30

Light Curtain Multi-Function Control Module User Manual

Original instructions

Figure 41: Specification window “Muting Micro 400”

A detailed description of “Muting” is given in

chapter 5.6 on page 37.

5.4.10. Muting other device (OSSDs)

Figure 42: Specification window “Muting other device (OSSDs)”

The MSR42 controller also offers the possibility of connecting one GuardShield safety light curtain or one laser scanner for muting applications. Due to
the limited number of GPIO’s, only two sensor T-type, and two sensor L-type muting is possible with this configuration type. The time sequences
which can be adjusted are equal to those for the muting of a Micro 400 system and are described in

chapter 5.6 on page 37. The only difference is that

instead of the Micro 400 safety light curtain now the non-Micro 400 safety light curtain is muted.

5.4.11. Function “EDM” + “Start Release”

High energy applications with very high power ratings require switching circuits with corresponding switching capacities. If the switching capacity of
the integrated OSSD outputs and/or extension relay module are insufficient, then external force guided, power contactors must be used, whose
function is monitored using contact feedback. This function is called EDM (= External Device Monitoring) and is found by clicking on the “Safety
Outputs OSSD” Edit button (3,

Figure 25).