Light Curtain Multi-Function Control Module User Manual

Original instructions

Figure 58: Configuration window for “Two sensor T-type” muting with 1 device (OSSD’s) safety device

Figure 59 shows the wiring diagram for an example of a MSR42 control unit configured with the “two sensor, T-type” muting mode.

For this muting mode two mute disable inputs may be configured. If selected, these signals must be “high” in order for a mute condition to take place
(See chapter 5.6.7 on page 39).

Figure 59: Wiring diagram for “two sensor T-type” muting with Micro 400 and disabling signals

5.6.11. Setup: four sensor T-type

Figure 60 shows a schematic arrangement for a four sensor, parallel beam, bidirectional muting application: “four sensor T-type.” Only the Micro 400
may be used in this mode.