Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 118

Advertising
background image

Publication GMSI10-UM010C-EN-P - May 2010

110 Wiring Connections for Previous Module Revisions

WARNING

EXPLOSION HAZARD

Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.

Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate
to this equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.

Terminal Block Assignments

No.

Name

Description

0

Xducer 1 (+)

Vibration transducer 1 connection

1

Xducer 2 (+)

Vibration transducer 2 connection

2

Buffer 1 (+)

Vibration signal 1 buffered output

3

Buffer 2 (+)

Vibration signal 2 buffered output

4

Tach/Signal In (+)

Tachometer transducer/signal input, positive side

5

Xducer Vin

Vibration transducer power input

6

Xducer V (+)

Vibration transducer power supply output, positive side connect
to Xducer Vin for positive biased transducers or Xducer RTN for
negative biased transducers

7

TxD

PC serial port, transmit data

8

RxD

PC serial port, receive data

9

XRTN

1

Circuit return for TxD and RxD

10

Chassis

Connection to DIN rail ground spring or panel mounting hole

11

4-20 mA 1 (+)

4-20 mA output
300 ohm maximum load

12

4-20 mA 1 (-)

13

Chassis

Connection to DIN rail ground spring or panel mounting hole

14

Chassis

Connection to DIN rail ground spring or panel mounting hole

15

Chassis

Connection to DIN rail ground spring or panel mounting hole

16

Xducer 1 (-)

1

Vibration transducer 1 connection

17

Xducer 2 (-)

1

Vibration transducer 2 connection

18

Signal Common

1

Vibration buffered output return

19

TACH Buffer

Tachometer transducer/signal output

20

Tachometer (-)

Tachometer transducer/signal input, negative side and TACH
Buffer return

21

Xducer V (-)

Vibration transducer power supply output, negative side connect
to Xducer RTN for positive biased transducer or Xducer Vin for
negative biased transducers and power

22

Xducer RTN

Vibration transducer power return

Advertising