Publication GMSI10-UM010C-EN-P - May 2010

Installing the XM-120 Eccentricity Module 39

Relay Indicator

Basic Operations

Powering Up the Module

The module performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.

The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Refer to Module Indicators on page 37 for more information about the LED
indicators.

Manually Resetting Relays

The XM-120 has an external reset switch located on top of the module, as
shown in Figure 2.24.

Color

State

Description

Red

Off

On-board relay is not activated.

Solid

On-board relay is activated.

MS Indicator State

Description

Flashing Red and Green

Device self-test is in progress.

Solid Green or Flashing Green

Device self-test completed successfully,
and the firmware is valid and running.

Flashing Red

Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the
firmware download is in progress.

Solid Red

Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.