Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 31

Advertising
background image

Publication GMSI10-UM010C-EN-P - May 2010

Installing the XM-120 Eccentricity Module 23

Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.

Figure 2.9 Relay Connection - Failsafe, Nonalarm Condition

Non-failsafe, Alarm Condition

Table 2.1 Relay Connections for XM-120

Configured for

Failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed Opened

COM

47

50

NO

48

49

Opened

Closed

COM 47

50

NC

46

51

Configured for

Non-failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed

Opened

COM

47

50

NC

46

51

Opened

Closed

COM

47

50

NO

48

49