Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 39

Advertising
background image

Publication GMSI10-UM010C-EN-P - May 2010

Installing the XM-120 Eccentricity Module 31

Figure 2.19 Remote Relay Reset Signal Connection

A single switch contact can also be shared by multiple XM modules wired in
parallel as shown in Figure 2.20.

Figure 2.20 Typical Multiple XM Modules Remote Relay Reset Signal Connection

ATTENTION

The Switch Input circuits are functionally isolated from
other circuits. It is recommended that the Switch RTN
signal be grounded at a signal point. Connect the Switch
RTN signal to the XM terminal base (Chassis terminal) or
directly to the DIN rail, or ground the signal at the switch
or other equipment that is wired to the switch.

ATTENTION

The relay reset connections may be different for different
XM modules. Figure 2.20 applies only to the XM-120
module. Refer to the installation instructions for the
module for its terminal assignments.

Advertising