Publication GMSI10-UM010C-EN-P - May 2010

20 Installing the XM-120 Eccentricity Module

1

Terminals are internally connected and isolated from the Chassis terminals.

22

Buffer Power 2 IN

Channel 2 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for
negative biased transducers

23

CAN_High

DeviceNet bus connection, high differential (white wire)

24

CAN_Low

DeviceNet bus connection, low differential (blue wire)

25

+24 V Out

Internally connected to 24 V In (terminal 44)
Used to daisy chain power if XM modules are not plugged into each other

26

DNet V (+)

DeviceNet bus power input, positive side (red wire)

27

DNet V (-)

DeviceNet bus power input, negative side (black wire)

28

24 V Common

1

Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal

29

4-20 mA 2 (+)

4-20 mA output
300 ohm maximum load

30

4-20 mA 2 (-)

31

Chassis

Connection to DIN rail ground spring or panel mounting hole

32

Chassis

Connection to DIN rail ground spring or panel mounting hole

33

Chassis

Connection to DIN rail ground spring or panel mounting hole

34

Chassis

Connection to DIN rail ground spring or panel mounting hole

35

Chassis

Connection to DIN rail ground spring or panel mounting hole

36

Chassis

Connection to DIN rail ground spring or panel mounting hole

37

Chassis

Connection to DIN rail ground spring or panel mounting hole

38

Chassis

Connection to DIN rail ground spring or panel mounting hole

39

Not Used

40

Switch RTN

Switch return, shared between SetPtMult and Reset Relay

41

Reset Relay

Switch input to reset internal relay (active closed)

42

Reserved

43

24 V Common

1

Internally DC-coupled to circuit ground

44

+24 V In

Connection to primary external +24 V power supply, positive side

45

24 V Common

1

Connection to external +24 V power supply, negative side (internally
DC-coupled to circuit ground)

46

Relay N.C. 1

Relay Normally Closed contact 1

47

Relay Common 1

Relay Common contact 1

48

Relay N.O. 1

Relay Normally Open contact 1

49

Relay N.O. 2

Relay Normally Open contact 2

50

Relay Common 2

Relay Common contact 2

51

Relay N.C. 2

Relay Normally Closed contact 2

Terminal Block Assignments

No.

Name

Description