Publication GMSI10-UM010C-EN-P - May 2010

Configuration Parameters 49

Alarm Parameters

The Alarm parameters control the operation of the alarms (alert and danger
level) and provide alarm status. The Eccentricity module provides two alarms,
one per eccentricity channel. Use the parameters to configure which
eccentricity measurement the alarm is associated with, as well as the behavior
of the alarm.

Trigger Slope

The input signal slope to be used as the trigger value
when in Manual Trigger mode.

Options: Positive

Negative

Note: This value is not used in Auto
Trigger mode.

Tachometer Signal Processing Parameters

Parameter Name

Description

Values/Comments

Alarm Parameters

Parameter Name

Description

Values/Comments

Number (1-2) (XM Serial
Configuration Utility only)

The alarm to be configured in the XM Serial
Configuration Utility. There are two alarms in the
Eccentricity module, one for each eccentricity
channel.

Options: 1 (Channel 1 alarm)

2 (Channel 2 alarm)

Name (XM Serial Configuration
Utility only)

A descriptive name to identify the alarm in the XM
Serial Configuration Utility.

Maximum 18 characters

Enable

Enable/disable the selected alarm.

Note: The Alarm Status is set to "Disarm" when the
alarm is disabled.

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled