Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 27

Advertising
background image

Publication GMSI10-UM010C-EN-P - May 2010

Installing the XM-120 Eccentricity Module 19

WARNING

EXPLOSION HAZARD

Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.

Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate
to this equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.

Terminal Block Assignments

No.

Name

Description

0

Xducer 1 (+)

Vibration transducer 1 connection

1

Xducer 2 (+)

Vibration transducer 2 connection

2

Buffer 1 (+)

Vibration signal 1 buffered output

3

Buffer 2 (+)

Vibration signal 2 buffered output

4

Tach/Signal In (+)

Tachometer transducer/signal input, positive side

5

Buffer Power 1 IN

Channel 1 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for
negative biased transducers

6

Positive Buffer Bias

Provides positive (-5 V to +24 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) or 22 (CH 2) for positive bias transducers

7

TxD

PC serial port, transmit data

8

RxD

PC serial port, receive data

9

XRTN

1

Circuit return for TxD and RxD

10

Chassis

Connection to DIN rail ground spring or panel mounting hole

11

4-20 mA 1 (+)

4-20 mA output
300 ohm maximum load

12

4-20 mA 1 (-)

13

Chassis

Connection to DIN rail ground spring or panel mounting hole

14

Chassis

Connection to DIN rail ground spring or panel mounting hole

15

Chassis

Connection to DIN rail ground spring or panel mounting hole

16

Xducer 1 (-)

1

Vibration transducer 1 connection

17

Xducer 2 (-)

1

Vibration transducer 2 connection

18

Signal Common

1

Vibration buffered output return

19

TACH Buffer

Tachometer transducer/signal output

20

Tachometer (-)

Tachometer transducer/signal return, TACH Buffer return

21

Buffer/Xducer Pwr (-) Provides negative (-24 V to +9 V) voltage compliance to buffered outputs

Connect to terminals 5 (CH 1) or 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external
sensor (40 mA maximum load)

Advertising