WARNING:

Before performing service or maintenance

operations on the system, turn off main power to unit and
install lockout tag or electrical shock could result.

1. Open all electrical disconnects and install lockout tag before

starting any service work.

2. Remove indoor coil access panel (See Fig. 12).
3. Locate lances in unit base insulation that are placed over the

perimeter of the vertical duct opening cover (See Fig. 13).

4. Using a straight edge and sharp knife, cut and remove the

insulation around the perimeter of the cover. Remove the
screws securing the cover to the unit base and slide out the
cover. Discard the cover.

5. Remove indoor blower access panel (See Fig. 14).

6. Disconnect indoor-fan motor leads from indoor fan relay

and unit contactor (See Fig. 15). Carefully disengage wire
tie containing indoor-fan motor leads from the unit control
box (See Fig. 15 & 17).

7. Remove screws securing indoor blower housing to blower

shelf and carefully slide out blower housing. There is a filler
bracket attached to the blower shelf; remove this filler
bracket and retain for later use (See Fig. 16).

8. Locate lances in unit base insulation that are placed over the

perimeter of the vertical discharge opening cover (See Fig.
13).

9. Using a straight edge and sharp knife, cut the insulation

around the perimeter of the cover. Remove the screws

TABLE 1—PHYSICAL DATA—UNIT 657A

UNIT SIZE

024

030

036

042

048

060

NOMINAL CAPACITY (ton)

2

2-1/2

3

3-1/2

4

5

OPERATING WEIGHT (lb.)

Without Base Rails

WIth Optional Rails

309
296

340
327

368
355

368
355

411
398

425
412

COMPRESSOR

Scroll

REFRIGERANT (R-22)

Quantity (lb.)

5.4

5.6

8.6

6.8

7.9

8.1

REFRIGERANT METERING DEVICE

Acutrol™ System

OUTDOOR COIL

Rows...Fins/in.

Face Area (sq. ft.)

2...17

7.0

2...17

7.0

2...17

8.7

2...17

8.7

2...17

8.7

2...17

8.7

OUTDOOR FAN

Nominal Cfm

Diameter (in.)

Motor Hp (Rpm)

2200

20

1/4 (1100)

2200

20

1/4 (1100)

2200

20

1/4 (1100)

2400

20

1/4 (1100)

2400

20

1/3 (1100)

2400

20

1/3 (1050)

INDOOR COIL

Rows...Fins/in.

Face Area (sq. ft.)

3...15

3.6

3...15

3.6

4...15

4.5

4...15

4.5

4...15

4.5

4...15

4.5

INDOOR BLOWER

Motor Type

Speeds

Nominal Airflow (Cfm)

Size (in.)

Motor Hp (RPM)

PSC

3

800

10x9

1/4 (1075)

PSC

3

1000
10x9

1/4 (1075)

PSC

3

1300
10x9

1/2 (1100)

PSC

3

1400
10x9

1/2 (1100)

ECM

Variable

1550

10x10

1.0 (Variable)

ECM

Variable

1800

10x10

1.0 (Variable)

RETURN-AIR FILTERS (in.)

Throwaway

24x24x1

24x24x1

24x30x1

24x30x1

24x30x1

24x30x1

ECM-Electronic Computated Motor.

Fig. 19—Area Not To Be Drilled

C95012

5"

[127]

19-

1/2

"

[495]

NOTES:

1.

Do not drill more than 1/2-in into shaded area.

2.

Dimensions in [ ] are in mm.

—12—