Forward claim papers directly to transportation company. Manu-
facturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest distributor if any item is missing. To prevent loss or
damage, leave all parts in original packages until installation.

II.

PROVIDE UNIT SUPPORT

A.

ROOF CURB & SLAB MOUNT

ROOF CURB - Install accessory roof curb in accordance with
instructions shipped with curb (See Fig. 6). Install insulation, cant
strips, roofing, and flashing. Ductwork must be attached to curb.

IMPORTANT:

The gasketing of the unit to the roof curb is

critical for a watertight seal. Install gasketing material supplied
with the roof curb. Improperly applied gasketing also can result in
air leaks and poor unit performance.

Curb should be level to within 1/4 in (See Fig. 8). This is necessary
for unit drain to function properly. Refer to accessory roof curb
installation instructions for additional information as required.

SLAB MOUNT - Place the unit on a solid, level concrete pad that
is a minimum of 4 in. thick with 2 in. above grade (See Fig. 10).
The slab should extend approximately 2 in. beyond the casing on
all 4 sides of the unit. Install a 6-in. gravel apron in front of

Fig. 3— 657A024-030 Unit Dimensions (with base rails)

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

CORNER WT

LB/KG

CENTER OF GRAVITY

IN/MM

lb.

kg

A

B

C

D

X

Y

Z

657A024

208/230-1-60

277

126

62/28

74/34

80/36

61/28

20.2/515

21.3/541

13.8/351

657A030

208/230-1-60

308

140

61/28

92/42

79/36

76/35

20.2/514

21.5/547

13.8/351