TABLE 14—TROUBLESHOOTING CHART

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan
will not start

Power Failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective thermostat, contactor, transformer,
control relay, defrost board, or high pressure or loss-
of-charge/low pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

Thermostat setting too high

Lower thermostat setting below room
temperature

Compressor will not start but condenser fan
runs

Faulty wiring or loose connections in compressor
circuit

Check wiring and repair or replace

Compressor motor burned out, seized, or
internal overload open

Determine cause.
Replace compressor

Defective run capacitor, overload, or PTC
(positive temperature coefficient) thermistor

Determine cause and replace

Low input voltage (20 percent low)

Determine cause and correct

Compressor cycles (other than normally
satisfying thermostat)

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and
recharge to capacities shown on nameplate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start
relay

Determine cause and replace

Defective thermostat

Replace thermostat

Faulty outdoor-fan motor or capacitor

Replace

Damaged reversing valve

Determine cause and correct

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

Thermostat set too low

Reset thermostat

Low refrigerant charge

Locate leak, repair, and recharge

Frosted coil with incorrect defrost operation

Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary

Air in system

Recover refrigerant, evacuate system,
and recharge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system,
and recharge

(Heat) Indoor air restricted or recirculating

Determine cause and correct

Indoor or outdoor air restricted or air short-cycling

Determine cause and correct

TABLE 14—TROUBLESHOOTING CHART (CONT’D)

SYMPTOM

CAUSE

REMEDY

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes
between defrost cycles

(Cool) High Heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

(Cool) Dirty air filter

Replace filter

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes
between defrost cycles

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

(Cool) Insufficient coil airflow

Increase air quantity
Check filter–replace if necessary

(Cool) Temperature too low in conditioned area

Reset thermostat

(Cool) Outdoor ambient below 40°F

Install low-ambient kit

Filter-drier restricted

Replace

Compressor runs but

outdoor fan does not

NC (normally closed) contacts on defrost board
open

Check condition of relay on board
Replace if necessary

IFM does not run

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly sealed

Connectors should snap easily; do not force

IFM operation is intermittent

Water dripping into motor

Verify proper drip loops in connector wires

Connectors not firmly sealed

Gently pull wires individually to be sure they are
crimped into the housing

IFM (048–060) runs when

it should be off

Motor programmed with a delay profile

Allow a few minutes for motor to shut off

With thermostat in “off” mode, the voltage on

G, Y1, Y2, W with respect to common, should be
1/2 of actual low voltage supply

If measured voltage is more that 1/2, the thermostat

is incompatible with motor. If voltage is less than

1/2, the motor has failed

IFM–Indoor Fan Motor