Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A User Manual

Page 18

Advertising
background image

B.

START UP AND MAKE ADJUSTMENTS

CAUTION:

Complete the required procedures given in

the Pre-Start- Up section before starting the unit. Do not
jumper any safety devices when operating the unit. Do
not operate the compressor when the outdoor temperature
is below 40°F (unless accessory low-ambient kit is
installed). Do not rapid-cycle the compressor. Allow 5
minutes between “on” cycles to prevent compressor
damage.

C.

CHECKING COOLING CONTROL OPERATION

Start and check the unit for proper cooling control operation as
follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room tem-
perature. Observe that compressor, outdoor fan, and indoor
blower motors start. Observe that compressor and outdoor
fan shut down when control setting is satisfied and that
indoor blower shuts down after fan time delay expires.

3. When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in heating mode when tempera-
ture control is set to “call for heating” (above room
temperature) and operates in cooling mode when tempera-
ture control is set to “call for cooling” (below room
temperature).

D.

CHECKING HEATING CONTROL OPERATION

Start and check the unit for proper cooling control operation as
follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.

2. Place SYSTEM switch in HEAT position and FAN switch

in AUTO position. Set cooling control above room tem-
perature. Observe that compressor, outdoor fan, and indoor
blower motors start. Observe that compressor and outdoor
fan shut down when control setting is satisfied and that
indoor blower shuts down after fan time delay expires.

3. When using an auto-changeover room thermostat, place

both SYSTEM and FAN switches in AUTO positions.
Observe that unit operates in heating mode when tempera-
ture control is set to “call for heating” (above room
temperature).

4. If system is equipped with supplemental or emergency heat

(resistance heaters), observe that when thermostat is placed
in EMERGENCY HEAT mode and temperature control is
set above room temperature that heaters and indoor blower
come on. Observe that heaters shut off when control setting
is satisfied and that the indoor blower shuts off after fan
time delay expires.

E.

CHECKING

AND

ADJUSTING

REFRIGERANT

CHARGE

The refrigerant system is fully charged with R-22 refrigerant,
tested, and factory-sealed.

NOTE:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the
compressor access panel. The chart includes the required suction
line temperature at given suction line pressures and outdoor
ambient temperatures (See Table 13A-H and Fig. 30).
An accurate superheat, thermocouple- or thermistor-type ther-
mometer, a sling psychrometer, and a gauge manifold are required
when using the superheat charging method for evaluating the unit
charge. Do not use mercury or small dial-type thermometers
because they are not adequate for this type of measurement.

Fig. 24—High-Voltage Connections

C99057

GROUND LUG

(IN SLPICE BOX)

BLU

YEL

BLK

GROUND

LEAD

SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC

3-PHASE
CONNECTIONS

LEGEND
NEC – National Electrical Code

Field Wiring
Splice Connections

NOTE: Use copper wire only.

L1

L3

L2

Fig. 25—Fan Blade Clearance

C95027

1/2 IN. MAX
FR OM FAN DECK

MOTOR SHAFT

MOTOR

—18—

Advertising