E.

OUTDOOR FAN

CAUTION:

Keep the outdoor fan free from all obstruc-

tions to ensure proper cooling operation. Never place
articles on top of the unit. Damage to unit may result.

1. Remove 2 screws at bottom of outdoor air intake grille and

remove plastic grille.

2. Inspect the fan blades for cracks or bends.

3. If fan needs to be removed, loosen the setscrew and slide

the fan off the motor shaft.

4. When replacing fan blade, position blade so that the leading

edge is 2-in. back from outdoor inlet grille or 1/2-in.
maximum fro fan deck (See Fig. 25).

5. Ensure that setscrew engages the flat area on the motor shaft

when tightening

6. Replace grille.

F.

ELECTRICAL CONTROLS AND WIRING

Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit and install lockout
tag.
Remove the control/blower and compressor compartment access
panels to locate all the electrical controls and wiring. Check all
electrical connections for tightness. Tighten all screw connections.
If any smoky or burned connections are noticed, disassemble the
connection, clean all the parts, restrip the wire end and reassemble
the connection properly and securely.
After inspecting the electrical controls and wiring, replace the
access panel. Start the unit, and observe at least one complete
heating cycle and one complete cooling cycle to ensure proper
operation. If discrepancies are observed in either or both operating
cycles, or if a suspected malfunction has occurred, check each
electrical component with the proper electrical instrumentation.
Refer to the unit wiring label when making these checkouts.

NOTE:

Refer to the heating and/or cooling sequence of operation

in this publication as an aid in determining proper control
operation

TABLE 13H—SUPERHEAT CHARGING TABLE, UNIT 060

TEMP (F)

AIR ENT

COND

EVAP AIR – CFM

1800

EVAP AIR – Ewb (F)

56

58

60

62

64

66

68

70

72

74

76

65

SPH

21.0

21.0

21.0

22.8

24.7

26.5

27.8

29.1

30.4

29.5

28.6

70

16.5

16.5

16.5

18.8

21.1

23.5

25.2

27.0

28.8

28.2

27.6

75

12.0

12.0

12.0

14.8

17.6

20.4

22.7

24.9

27.2

26.9

26.6

80

10.5

10.5

10.5

12.7

14.9

17.1

19.8

22.5

25.2

25.4

25.5

85

9.0

9.0

9.0

10.6

12.3

13.9

17.0

20.0

23.1

23.8

24.5

90

4.5

4.5

4.5

6.5

8.5

10.5

14.3

18.1

21.9

22.7

23.5

95

4.8

7.2

11.7

16.2

20.7

21.6

22.5

100

3.6

8.6

13.6

18.6

20.0

21.4

105

5.5

11.1

16.6

18.5

20.4

110

10.0

15.5

17.5

19.4

115

9.2

14.7

16.5

18.5

Ewb-Entering Wet Bulb
SPH-Superheat at Compressor (F)
– -Do not attempt to charge system under these conditions as refrigerant slugging may occur.

Fig. 30—Required Suction Tube Temperature (F) *

C95030

Required Suction Tube Temperature

SUPERHEAT

TEMP (F)

SUCTION PRESSURE AT SERVICE PORT (Psig)

61.5

64.2

67.1

70

73

76

79.2

82.4

85.7

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

32

67

69

71

73

75

77

79

81

83

34

69

71

73

75

77

79

81

83

85

36

71

73

75

77

79

81

83

85

87

38

73

75

77

79

81

83

85

87

89

40

75

77

79

81

83

85

87

89

91

NOTE: Measure suction tube temperature with accurate superheat ther-
mometer or thermistor-type thermometer

—28—