WARNING:

Disconnect and tag electrical power to the

unit before cleaning the blower motor and wheel. Failure
to adhere to this warning could cause personal injury or
death.

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. For PSC Blower Motors Disconnect motor lead from

indoor fan relay (IFR). Disconnect yellow lead from
terminal L2 of the contactor.

TABLE 10—WET COIL PRESSURE DROP

UNIT SIZE

AIRFLOW

(CFM)

PRESSURE DROP

(IN. WG)

024

600

0.039

700

0.058

800

0.075

900

0.088

030

900

0.088

1000

0.095

1200

0.123

036

1000

0.068

1200

0.088

1400

0.108

1600

0.123

042

1000

0.048

1200

0.069

1400

0.088

1600

0.102

048

1400

0.068

1550

0.073

1600

0.075

1800

0.088

060

1700

0.082

1900

0.095

2100

0.108

2300

0.123

TABLE 11—ACCESSORY ELECTRIC HEATER PRESSURE DROP (IN. WG)

HEATER

KW

CFM

600

800

1000

1200

1400

1600

1800

2000

2200

5–20

0.030

0.033

0.037

0.042

0.047

0.052

0.060

0.067

0.075

TABLE 12—FILTER PRESSURE DROP (IN. WG)

UNIT SIZE

FILTER

SIZE

(IN.)

500 600 700

800

900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

024–036

24 x 24 x 1

0.06 0.06 0.07 0.07

0.08

0.09

0.10

042–060

24 x 30 x 1

0.08

0.09

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.17

0.18

TABLE 13A—SUPERHEAT CHARGING TABLE, UNIT 024–311

TEMP (F)

AIR ENT

COND

EVAP AIR – CFM

800

EVAP AIR – Ewb (F)

56

58

60

62

64

66

68

70

72

74

76

65

SPH

24.0

27.4

30.8

31.1

31.5

30.5

29.5

29.2

28.9

70

19.5

24.4

29.3

29.9

30.4

29.5

28.6

28.2

27.8

75

15.0

21.4

27.8

28.6

29.4

28.5

27.7

27.2

26.7

80

7.5

14.4

21.4

24.5

27.6

27.1

26.5

26.1

25.6

85

7.5

15.0

20.4

25.8

25.6

25.4

24.9

24.5

90

7.5

14.0

20.4

22.3

24.2

23.8

23.4

95

7.5

15.0

19.0

23.1

22.7

22.3

100

7.5

13.5

19.5

20.3

21.1

105

8.0

16.0

18.0

20.0

110

12.4

15.7

18.9

115

8.9

13.3

17.8

Ewb-Entering Wet Bulb
SPH-Superheat at Compressor (F)
– -Do not attempt to charge system under these conditions as refrigerant slugging may occur.