Fig. 32—Typical Heat Pump Operation-Heating Mode

C95045

STRAINER

ACCUMULA

T

O

R

COMPRESSOR

STRAINER

LCS

OUTDOOR COIL

INDOOR COIL

A

B

D

C

Check Valves

A

Open

B

Closed

C

Open

D

Closed

LEGEND

LCS

Loss of Charge Switch

Acutrol

Metering Device

Check Valve (Arrow indicates direction of flow)

HEATING CYCLE

1. Hot gas from compressor flows through the 4-way valve and is

directed to the cooling liquid line check valve. It is then condensed
and directed through subcooling circuits and out to the strainer
and the check valve in the heating liquid line.

2. The refrigerant then feeds the outdoor coil through the Acutrol

metering device on each circuit.

3. Each circuit evaporates the refrigerant and the circuits are com-

bined in the outdoor header with some of the circuits flowing through
the check valve.

4. The refrigerant then flows through the 4-way valve, accumulator,

and back to the compressor.