GROSS COOLING CAPACITIES (cont)

579F216 (18 TON)

Air Entering

Evaporator

Air Entering Condenser (F)

75

85

95

105

Cfm

BF

Ewb

(F)

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Capacity MBtuh Compressor

kW

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

5400

0.035

72

233.0

116.7

15.42

226.0

115.2

16.88

217.0

112.4

18.25

206.7

109.0

19.54

67

215.0

148.3

14.99

208.9

145.7

16.35

200.0

142.3

17.66

188.3

138.2

18.94

62

198.8

178.0

14.54

191.1

174.5

15.80

181.3

170.0

17.04

170.3

164.3

18.25

6300

0.045

72

237.0

123.8

15.57

230.0

120.9

16.99

221.0

119.0

18.40

210.9

115.6

19.75

67

221.0

159.2

15.15

212.7

156.6

16.52

204.3

153.3

17.86

193.4

149.7

19.05

62

204.5

193.0

14.73

196.6

189.1

16.03

187.5

184.3

17.31

176.9

176.7

18.57

7200

0.055

72

240.0

132.9

15.66

234.0

126.8

17.13

224.0

125.3

18.55

213.4

122.6

19.94

67

223.0

170.1

15.26

216.0

167.2

16.65

207.8

164.2

18.00

196.8

160.2

19.22

62

209.6

206.1

14.90

202.0

201.2

16.24

194.2

194.0

17.54

185.7

185.6

18.83

8100

0.065

72

239.0

141.6

15.65

236.0

133.0

17.21

227.0

131.4

19.67

216.0

128.7

20.01

67

227.0

180.3

15.36

219.0

176.9

16.73

209.3

174.2

18.07

199.0

170.6

19.38

62

214.6

214.4

15.04

207.6

207.4

16.41

199.8

199.8

17.74

191.0

190.9

19.03

9000

0.075

72

241.0

148.1

15.75

237.0

139.6

17.24

229.0

136.5

18.74

217.0

133.9

20.01

67

227.0

191.2

15.38

221.0

186.9

16.80

211.3

183.7

18.14

200.7

180.0

19.42

62

217.0

217.0

15.12

212.4

211.1

16.55

204.0

203.9

17.91

195.1

195.0

19.22

579F216 (18 TON) (cont)

Air Entering

Evaporator

Air Entering Condenser (F)

115

125

Cfm

BF

Ewb

(F)

Capacity MBtuh

Compressor

kW

Capacity MBtuh

Compressor

kW

Total

Sensible

Total

Sensible

5400

0.035

72

195.4

104.8

20.77

183.9

100.8

21.80

67

178.7

134.2

20.10

167.2

129.8

21.25

62

159.1

157.9

19.40

151.1

151.1

20.61

6300

0.045

72

199.7

111.8

20.95

187.1

107.6

22.10

67

183.0

145.7

20.31

171.8

141.4

21.50

62

169.0

168.9

19.74

160.2

160.1

21.02

7200

0.055

72

203.3

119.3

21.25

189.5

114.3

22.30

67

185.9

156.3

20.48

174.4

152.1

21.60

62

176.3

176.3

20.09

167.6

167.5

21.25

8100

0.065

72

204.1

124.9

21.27

191.5

120.6

22.40

67

187.9

166.4

20.55

176.9

161.6

21.70

62

182.0

182.0

20.30

172.7

172.6

21.60

9000

0.075

72

206.1

131.3

21.40

193.4

127.0

22.60

67

189.8

175.8

20.71

178.9

169.9

21.90

62

186.1

186.0

20.50

176.3

176.3

21.70

LEGEND

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

kW

Compressor Motor Power Input

MBtuh — Btuh in thousands

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

sensible capacity (1000 x MBtuh)

t

= t

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air

lwb

leaving evaporator coil (h

)

lwb

total capacity (1000 x MBtuh)

h

= h

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil.

ewb

3. The sensible heat capacity is based on 80 F entering dry-bulb (edb) tempera-

ture of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from the sensible heat capacity.

Above 80 F edb, add (corr factor x cfm) to the sensible heat capacity.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

28