Bryant 579F User Manual

Page 49

Advertising
background image

AIR QUANTITY LIMITS

UNIT

MINIMUM CFM

MAXIMUM CFM

580D036

900

1500

580D048

1200

2000

580D060

1500

2500

580D072

1800

3000

580D090

2250

3750

580D102

2550

4250

UNIT

MINIMUM CFM

MAXIMUM CFM

580D120

3000

5,000

580D150

3750

6,250

579F180

4500

7,500

579F216

5400

9,000

579F240

6000

10,000

579F300

7500

11,250

SOUND POWER (Total Unit)

UNIT

SOUND

RATING

(60 Hz)

A-WEIGHTED

(dB)

OCTAVE BANDS

63

125

250

500

1000

2000

4000

8000

580D036-060

8.2 Bels

80.5

56.8

75.8

72.4

72.9

74.8

75.4

71.3

69.1

580D072

8.4 Bels

82.4

56.0

69.8

72.9

75.9

78.3

76.5

72.6

67.9

580D090,102

8.6 Bels

86.4

83.2

87.4

83.5

82.8

83.0

77.7

71.8

67.0

580D120

8.8 Bels

87.6

97.6

90.4

85.7

84.8

83.9

77.5

71.3

65.8

580D150

8.8 Bels

86.4

83.7

87.2

83.4

82.8

83.0

77.7

71.8

67.0

579D180

8.8 Bels

87.3

87.1

89.9

86.4

84.0

82.7

79.0

73.9

68.6

579D216

8.8 Bels

87.2

91.1

88.1

89.0

84.7

82.0

76.9

74.1

68.2

579D240

9.4 Bels

94.3

99.6

92.8

94.2

91.8

89.8

85.5

81.0

75.2

579D300

9.5 Bels

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

Bels — Sound Levels (1 bel = 10 decibels)

579F180-300 HORIZONTAL SUPPLY/RETURN FAN PERFORMANCE

WITH 389210-201 OR 389211-201 HIGH STATIC REGAIN ADAPTER

NOTE: The 389210-201 or 389211-201 high static regain adapter
accessory may be used to provide horizontal supply/return.

NOTE: The 389210-201 or 389211-201 horizontal supply/return
adapter accessory improves 579F180-300 fan performance by in-
creasing external static pressure by amount shown above.

49

Advertising