Bryant 579F User Manual

Page 60

Advertising
background image

APPLICATION DATA (cont)

EVAPORATOR-FAN MOTOR PERFORMANCE

UNIT

EVAPORATOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

580D036

Standard

208/230

0.34

440

2.9

460

1.4

575

1.4

Alternate

208/230

1.00

1000

5.4

460

2.3

575

2.3

580D048

Standard

208/230

0.75

850

3.5

460

1.8

575

1.8

Alternate

208/230

1.00

1000

5.4

460

2.3

575

2.3

580D060

Standard

208/230

1.20

1340

5.9

460

3.2

575

3.2

Alternate

208/230

1.80

1921

8.9

460

4.7

575

4.7

580D072

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D090

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D102

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

580D120

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

Alternate

208/230

2.90

2615

7.9

460

3.6

575

3.6

580D150

Standard

208/230

4.20

3775

11.1

460

5.0

575

5.0

Alternate

208/230

5.25

4400

15.0

460

7.4

575

7.4

579F180

Standard

208/230

4.25

3775

10.5

460

4.8

575

3.45

3065

3.9

579F216

Standard

208/230

5.90

5180

15.8

460

7.9

575

6.0

579F240

Standard

208/230

8.70

7915

22.0

460

9.50

8640

13.0

575

8.70

7915

10.0

579F300

Standard

208/230

10.20

9510

28.0

460

11.80

11,000

14.6

575

10.20

9510

13.0

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be

utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.