AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)

580D060 (5 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

Medium Speed

High Speed

208 V

230, 460, 575 V

208 V

230,460, 575 V

208 V

230, 460, 575 V

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1500

0.74

0.67

750

1.06

0.71

791

1.07

0.70

782

1.27

0.76

845

1.26

0.79

875

1.33

0.85

949

1600

0.54

0.70

780

0.90

0.74

824

0.92

0.74

821

1.13

0.79

883

1.14

0.82

913

1.22

0.89

988

1700

0.34

0.73

810

0.75

0.77

857

0.77

0.77

861

1.00

0.83

921

1.01

0.85

950

1.11

0.92

1027

1800

0.14

0.75

839

0.59

0.80

891

0.62

0.81

900

0.87

0.86

959

0.89

0.88

988

1.00

0.96

1066

1900

0.44

0.83

924

0.47

0.84

940

0.74

0.90

997

0.77

0.92

1025

0.89

0.99

1105

2000

0.28

0.86

957

0.32

0.88

979

0.61

0.93

1035

0.64

0.95

1063

0.78

1.03

1144

2100

0.13

0.89

990

0.17

0.91

1018

0.48

0.96

1073

0.51

0.99

1101

0.67

1.06

1183

2200

0.02

0.95

1058

0.35

1.00

1111

0.39

1.02

1138

0.56

1.10

1222

2300

0.22

1.03

1149

0.26

1.06

1176

0.45

1.13

1261

2400

0.09

1.07

1187

0.14

1.09

1213

0.34

1.17

1300

2500

0.23

1.20

1340

LEGEND

Bhp — Brake Horsepower Input to Fan
Esp

External Static Pressure (in. wg)

NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range

of the motor can be utilized with confidence. Using your fan motors up to the

wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

4. Minimum allowable cfm is 3000 cfm/ton.

580D060 (5 TON)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

730

0.34

357

789

0.40

420

896

0.53

557

990

0.67

704

1072

0.83

872

1153

1.00

1051

1600

770

0.40

420

826

0.46

483

931

0.61

641

1020

0.75

788

1101

0.91

956

1178

1.09

1145

1700

811

0.47

494

865

0.54

567

966

0.69

725

1051

0.84

883

1133

1.01

1061

1205

1.18

1240

1800

852

0.55

578

905

0.62

651

1002

0.78

820

1084

0.93

977

1163

1.10

1156

1235

1.29

1355

1900

894

0.54

567

945

0.72

757

1037

0.88

925

1119

1.04

1093

1194

1.21

1271

1266

1.40

1471

2000

936

0.74

778

984

0.82

862

1072

0.98

1030

1154

1.16

1219

1226

1.33

1397

1297

1.53

1608

2100

978

0.85

893

1024

0.93

977

1108

1.10

1156

1192

1.29

1355

1259

1.47

1545

1327

1.66

1744

2200

1021

0.97

1019

1064

1.05

1103

1145

1.22

1282

1225

1.43

1503

1294

1.62

1702

1359

1.80

1902

2300

1064

1.10

1156

1104

1.18

1240

1183

1.36

1429

1260

1.57

1650

1330

1.78

1870

1392

1.97

2070

2400

1107

1.24

1303

1145

1.32

1387

1222

1.45

1524

1296

1.73

1818

1365

1.94

2038

1426

2.15

2259

2500

1150

1.39

1460

1186

1.48

1555

1262

1.68

1765

1331

1.89

1986

1400

2.12

2227

1461

2.34

2459

580D060 (5 TON) (cont)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1221

1.17

1229

1256

1.30

1366

1283

1.32

1387

1303

1.22

1282

1600

1252

1.27

1334

1311

1.45

1524

1340

1.58

1660

1330

1.61

1692

1700

1278

1.37

1439

1345

1.57

1650

1397

1.76

1849

1424

1.89

1986

1800

1303

1.48

1555

1371

1.69

1776

1433

1.90

1996

1480

2.09

2196

1900

1330

1.59

1671

1396

1.80

1902

1460

2.03

2133

1517

2.25

2364

2000

1362

1.73

1818

1422

1.94

2038

1485

2.16

2270

1544

2.40

2522

2100

1393

1.87

1965

1452

2.08

2185

1510

2.31

2427

1570

2.55

2674

2200

1423

2.02

2122

1483

2.24

2354

1538

2.46

2585

1594

2.71

2821

2300

1454

2.18

2291

1515

2.41

2532

1571

2.64

2758

1623

2.88

2976

2400

1485

2.36

2480

1544

2.59

2721

1604

2.84

2947

1657

3.07

3152

2500

1518

2.55

2679

1574

2.78

2905

1633

3.03

3134

1692

3.28

3345

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates field-supplied drive required. (See Note 4.)

2.

indicates field-supplied motor and drive required.

3.

indicates maximum usable bhp/watts.

4. Alternate motor drive range: 900 to 1300 rpm. All other rpms require a field-

supplied drive.

5. Values include losses for filters, unit casing, and wet coils.

6. Maximum continuous bhp is 1.80 and maximum continuous watts are 1921.

Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

7. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

40