Air delivery — vertical discharge units – Bryant 579F User Manual

Page 30

Advertising
background image

AIR DELIVERY — VERTICAL DISCHARGE UNITS

580D036 (3 TON)

Airflow

(Cfm)

Standard Direct Drive Motor

Low Speed

High Speed

208 V

230, 460, 575 V

208 V

230, 460, 575 V

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

900

0.49

0.21

253

0.50

0.23

277

0.51

0.26

307

0.55

0.31

363

1000

0.42

0.23

270

0.43

0.25

292

0.43

0.27

321

0.51

0.32

374

1100

0.37

0.24

287

0.38

0.26

307

0.39

0.28

335

0.46

0.33

385

1200

0.33

0.26

304

0.33

0.27

323

0.34

0.29

349

0.40

0.34

397

1300

0.27

0.27

321

0.28

0.29

338

0.28

0.31

364

0.34

0.34

408

1400

0.20

0.29

338

0.23

0.30

354

0.25

0.32

378

1500

0.16

0.30

355

0.18

0.31

369

0.20

0.33

392

LEGEND

Bhp — Brake Horsepower Input to Fan
Esp

External Static Pressure (in. wg)

NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range

of the motor can be utilized with confidence. Using your fan motors up to the

wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

4. Minimum allowable cfm is 300 cfm/ton.

580D036 (3 TON)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

581

0.12

119

673

0.18

179

736

0.22

219

805

0.25

249

865

0.29

288

911

0.34

338

1000

644

0.19

189

709

0.22

219

782

0.28

279

835

0.30

298

900

0.35

348

937

0.38

378

1100

687

0.22

219

746

0.26

259

806

0.30

298

867

0.35

348

929

0.40

398

964

0.40

398

1200

733

0.26

259

785

0.32

318

843

0.35

348

903

0.41

408

960

0.47

467

994

0.50

497

1300

754

0.29

288

826

0.38

378

891

0.43

428

942

0.48

477

991

0.53

527

1047

0.60

597

1400

810

0.35

348

868

0.45

448

937

0.51

507

984

0.57

567

1032

0.62

617

1067

0.67

666

1500

841

0.42

418

911

0.53

527

985

0.61

607

1029

0.66

656

1073

0.72

716

1109

0.77

766

580D036 (3 TON) (cont)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.7

0.8

0.9

1.0

1.1

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

957

0.39

388

988

0.43

428

1039

0.47

448

1061

0.51

487

1083

0.54

527

1105

0.58

567

1000

992

0.44

438

1039

0.49

487

1061

0.55

507

1088

0.60

547

1111

0.66

587

1136

0.72

627

1100

1013

0.49

487

1068

0.55

547

1091

0.61

577

1109

0.66

607

1127

0.73

637

1145

0.80

666

1200

1045

0.56

557

1090

0.64

637

1109

0.68

647

1156

0.73

676

1203

0.81

706

1250

0.86

736

1300

1075

0.64

637

1122

0.70

696

1152

0.76

716

1190

0.82

756

1228

0.87

796

1266

0.94

836

1400

1110

0.73

726

1160

0.78

766

1181

0.83

806

1237

0.88

845

1293

0.94

885

1349

0.99

925

1500

1150

0.78

816

1190

0.84

855

1225

0.89

895

1271

0.95

945

1317

1.00

995

1383

1.05

1044

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 4.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Alternate motor drive range is 760 to 1000 rpm. All other rpms require a field-

supplied drive.

5. Values include losses for filters, unit casing, and wet coils.

6. Maximum continuous bhp is 1.0 and the maximum continuous watts are 1000.

Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

7. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

30