AIR DELIVERY — 579F180-300 UNITS

579F180 (15 TON)

Airflow

(Cfm)

Standard Belt-Drive Motor; 208/230-V and 460 V Units

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

801

1.05

933

890

1.26

1119

971

1.46

1297

1050

1.67

1483

1125

1.88

1670

1200

2.12

1883

4800

843

1.25

1110

928

1.47

1306

1006

1.68

1492

1081

1.90

1687

1153

2.13

1892

1223

2.36

2096

5100

885

1.47

1306

968

1.70

1510

1043

1.93

1714

1114

2.16

1918

1183

2.40

2131

1250

2.64

2345

5400

927

1.71

1519

1008

1.95

1732

1080

2.20

1954

1148

2.44

2167

1214

2.69

2389

1279

2.94

2611

5700

971

1.98

1758

1049

2.24

1989

1118

2.50

2220

1134

2.75

2442

1247

3.01

2673

1309

3.28

2913

6000

1016

2.28

2025

1091

2.55

2265

1158

2.83

2513

1222

3.10

2753

1282

3.36

2984

1342

3.64

3233

6300

1059

2.60

2309

1133

2.89

2567

1198

3.17

2815

1259

3.46

3073

1318

3.74

3321

1375

4.02

3570

6600

1104

2.96

2629

1174

3.26

2895

1239

3.56

3162

1297

3.86

3428

1355

4.15

3686

6900

1150

3.35

2975

1218

3.67

3259

1281

3.98

3535

7200

1194

3.77

3348

1260

4.10

3641

7500

1238

4.23

3758

579F180 (15 TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor; 208/230-V and 460-V Units

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1275

2.39

2123

1349

2.70

2398

1421

3.03

2691

1490

3.39

3011

4800

1293

2.62

2327

1364

2.92

2593

1433

3.24

2877

1501

3.59

3188

5100

1316

2.90

2575

1382

3.18

2824

1448

3.49

3099

1514

3.86

3428

5400

1342

3.20

2842

1403

3.47

3082

1466

3.77

3348

1529

4.16

3694

5700

1370

3.54

3144

1429

3.81

3384

1487

4.11

3650

6000

1401

3.92

3481

1458

4.20

3730

6300

6600

6900

7200

7500

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms require a

field-supplied drive.

2. Static pressure losses (i.e., economizer) must be added to external static pres-

sure before entering Air Delivery table.

3. Interpolation is permissible. Do not extrapolate.
4. Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775.

Extensive motor and drive testing on these units ensures that the full horse-
power range of the motor can be utilized with confidence. Using your fan mo-
tors up to the watts rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.

579F180 (15 TON)

Airflow

(Cfm)

Standard Belt-Drive Motor, 575-V Units

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

801

1.05

933

890

1.26

1119

971

1.46

1297

1050

1.67

1483

1125

1.88

1670

1200

2.12

1883

4800

843

1.25

1110

928

1.47

1306

1006

1.68

1492

1081

1.90

1687

1153

2.13

1892

1223

2.36

2096

5100

885

1.47

1306

968

1.70

1510

1043

1.93

1714

1114

2.16

1918

1183

2.40

2131

1250

2.64

2345

5400

927

1.71

1519

1008

1.95

1732

1080

2.20

1954

1148

2.44

2167

1214

2.69

2389

1279

2.94

2611

5700

971

1.98

1758

1049

2.24

1989

1118

2.50

2220

1134

2.75

2442

1247

3.01

2673

1309

3.28

2913

6000

1016

2.28

2025

1091

2.55

2265

1158

2.83

2513

1222

3.10

2753

1282

3.36

2984

6300

1059

2.60

2309

1133

2.89

2567

1198

3.17

2815

6600

1104

2.96

2629

1174

3.26

2895

6900

1150

3.35

2975

7200

7500

579F180 (15 TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor, 575-V Units

External Static Pressure (in. wg)

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1275

2.39

2123

1349

2.70

2398

1421

3.03

2691

1490

3.39

3011

4800

1293

2.62

2327

1364

2.92

2593

1433

3.24

2877

5100

1316

2.90

2575

1382

3.18

2824

5400

1342

3.20

2842

5700

6000

6300

6600

6900

7200

7500

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Factory shipped motor drive range is 1201 to 1462 rpm. Other rpms require a

field-supplied drive.

2. Static pressure losses (i.e., economizer) must be added to external static pres-

sure before entering Air Delivery table.

3. Interpolation is permissible. Do not extrapolate.
4. Maximum continuous bhp is 3.45 and the maximum continuous watts are 3065.

Extensive motor and drive testing on these units ensures that the full horse-
power range of the motor can be utilized with confidence. Using your fan mo-
tors up to the watts rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.