Air delivery — vertical discharge units (cont) – Bryant 579F User Manual

Page 31

Advertising
background image

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)

580D048 (4 TON)

Airflow

(Cfm)

Standard Direct Drive Motor

Low Speed

High Speed

208 V

230, 460, 575 V

208 V

230, 460, 575 V

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1200

0.68

0.41

458

0.74

0.45

506

0.74

0.51

572

0.85

0.56

632

1300

0.61

0.42

471

0.67

0.46

521

0.66

0.52

589

0.78

0.58

651

1400

0.53

0.45

503

0.59

0.49

556

0.59

0.54

616

0.70

0.60

681

1500

0.45

0.47

536

0.51

0.52

593

0.52

0.56

631

0.63

0.62

698

1600

0.36

0.49

557

0.42

0.54

616

0.45

0.58

654

0.56

0.64

723

1700

0.26

0.52

584

0.32

0.57

646

0.37

0.60

678

0.48

0.66

750

1800

0.15

0.54

610

0.22

0.60

674

0.30

0.62

698

0.41

0.68

772

1900

0.04

0.56

629

0.11

0.62

696

0.23

0.64

720

0.34

0.70

796

2000

0.16

0.66

744

0.26

0.73

823

LEGEND

Bhp — Brake Horsepower Input to Fan
Esp

External Static Pressure (in. wg)

NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range

of the motor can be utilized with confidence. Using your fan motors up to the

wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

4. Minimum allowable cfm is 300 cfm/ton.

580D048 (4 TON)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

596

0.20

210

665

0.25

263

722

0.31

320

779

0.36

378

872

0.48

504

915

0.54

567

957

0.60

630

1300

633

0.24

252

699

0.30

315

754

0.36

378

809

0.42

441

902

0.55

578

943

0.61

641

984

0.67

704

1400

672

0.30

315

735

0.36

378

788

0.42

441

840

0.48

504

933

0.62

651

972

0.69

720

1011

0.75

788

1500

711

0.35

368

770

0.42

441

822

0.49

510

873

0.55

578

963

0.69

725

1002

0.77

804

1041

0.84

858

1600

751

0.42

441

835

0.49

515

871

0.56

588

907

0.63

662

993

0.77

787

1033

0.85

869

1072

0.93

950

1700

791

0.49

515

873

0.57

599

907

0.65

678

941

0.72

757

1024

0.87

889

1064

0.96

976

1103

1.04

1063

1800

831

0.58

609

881

0.66

693

929

0.74

772

976

0.81

851

1057

0.97

991

1095

1.06

1078

1132

1.14

1165

1900

872

0.67

704

919

0.75

788

965

0.84

877

1011

0.92

967

1091

1.08

1104

1127

1.17

1191

1162

1.25

1277

2000

913

0.77

809

958

0.86

904

1002

0.95

993

1046

1.03

1082

1125

1.21

1237

1160

1.30

1323

1195

1.38

1410

580D048 (4 TON) (cont)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.9

1.0

1.1

1.2

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

993

0.65

678

1028

0.69

725

1056

0.72

751

1083

0.74

778

1134

0.80

935

1185

0.88

965

1331

0.99

1000

1300

1021

0.74

772

1058

0.80

841

1090

0.85

888

1121

0.89

935

1171

0.94

988

1219

1.00

999

1268

1.10

1029

1400

1049

0.82

837

1086

0.89

885

1120

0.96

950

1153

1.00

976

1210

1.12

1071

1257

1.17

1105

1307

1.25

1190

1500

1077

0.92

922

1113

0.99

985

1147

1.06

1054

1180

1.13

1081

1241

1.27

1215

1295

1.37

1294

1339

1.43

1350

1600

1107

1.00

998

1141

1.09

1084

1174

1.17

1134

1207

1.25

1196

1269

1.40

1339

1326

1.54

1454

1376

1.65

1558

1700

1137

1.12

1128

1171

1.20

1194

1203

1.29

1278

1235

1.37

1310

1296

1.53

1463

1354

1.70

1605

1407

1.84

1738

1800

1167

1.23

1239

1202

1.32

1313

1233

1.41

1398

1263

1.49

1425

1323

1.67

1597

1381

1.85

1747

1436

2.02

1907

1900

1197

1.35

1360

1232

1.45

1442

1263

1.54

1532

1294

1.63

1559

1351

1.81

1731

1408

2.00

1889

1463

2.19

2068

2000

1229

1.48

1491

1262

1.58

1572

1294

1.68

1671

1325

1.78

1702

1362

1.97

1884

1436

2.16

2040

1489

2.36

2229

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 4.)

2.

indicates field-supplied motor and drive required.

3.

indicates maximum usable bhp/watts.

4. Alternate motor drive range is 835 to 1185 rpm. All other rpms require a field-

supplied drive.

5. Values include losses for filters, unit casing, and wet coils.

6. Maximum continuous bhp is 1.0, and the maximum continuous watts are 1000.

Extensive motor and electrical testing on these units ensure that the full range
of the motor can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

7. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.

31

Advertising