AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)

580D048 (4 TON)

Airflow

(Cfm)

Standard Direct Drive Motor

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

Esp

Bhp

Watts

1200

0.75

0.41

458

0.81

0.45

506

0.87

0.51

572

0.92

0.56

632

1300

0.68

0.42

471

0.74

0.46

521

0.79

0.52

589

0.85

0.58

651

1400

0.60

0.45

503

0.66

0.49

556

0.71

0.54

616

0.77

0.60

681

1500

0.51

0.47

536

0.58

0.52

593

0.64

0.56

631

0.70

0.62

698

1600

0.42

0.49

557

0.49

0.54

616

0.56

0.58

654

0.63

0.64

723

1700

0.32

0.52

584

0.39

0.57

646

0.48

0.60

678

0.55

0.66

750

1800

0.21

0.54

610

0.29

0.60

674

0.41

0.62

698

0.48

0.68

772

1900

0.09

0.56

629

0.18

0.62

696

0.33

0.64

720

0.41

0.70

796

2000

0.06

0.65

731

0.26

0.66

744

0.33

0.73

823

LEGEND

Bhp — Brake Horsepower Input to Fan
Esp

External Static Pressure (in. wg)

NOTES:
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full range

of the motor can be utilized with confidence. Using your fan motors up to the

wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

4. Minimum allowable cfm is 300 cfm/ton.

580D048 (4 TON)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

569

0.18

189

641

0.23

242

701

0.29

299

761

0.34

357

859

0.46

483

901

0.52

546

943

0.58

609

1300

604

0.22

231

673

0.28

294

731

0.34

352

788

0.39

410

887

0.52

546

928

0.59

615

968

0.65

683

1400

640

0.27

284

705

0.33

347

761

0.39

410

817

0.45

473

914

0.59

620

955

0.66

688

996

0.72

757

1500

676

0.32

336

738

0.38

399

793

0.45

468

847

0.51

536

940

0.65

683

982

0.73

767

1024

0.81

851

1600

713

0.38

399

772

0.44

462

825

0.51

536

877

0.58

609

967

0.73

767

1009

0.81

851

1051

0.89

935

1700

750

0.45

473

806

0.51

536

857

0.59

615

908

0.66

693

997

0.81

851

1037

0.90

940

1077

1.01

1030

1800

788

0.52

546

841

0.59

620

890

0.67

704

939

0.75

788

1026

0.91

956

1065

1.01

1040

1104

1.07

1124

1900

826

0.60

630

876

0.68

714

924

0.76

799

971

0.84

883

1056

1.01

1061

1094

1.10

1151

1132

1.18

1240

2000

864

0.70

735

912

0.77

809

958

0.86

898

1004

0.94

988

1087

1.12

1177

1125

1.21

1271

1162

1.30

1366

580D048 (4 TON) (cont)

Airflow

(Cfm)

Alternate Belt Drive Motor

External Static Pressure (in. wg)

0.9

1.0

1.1

1.2

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

987

0.64

652

1030

0.70

695

1068

0.79

792

1106

0.87

889

1134

0.98

998

1189

1.12

1138

1245

1.21

1358

1300

1006

0.71

709

1044

0.77

736

1086

0.84

833

1128

0.91

930

1183

1.10

1052

1226

1.23

1215

1297

1.35

1406

1400

1033

0.79

797

1069

0.86

838

1104

0.93

925

1139

1.01

1012

1218

1.14

1090

1286

1.34

1282

1320

1.48

1463

1500

1060

0.88

891

1095

0.95

930

1129

1.02

1022

1162

1.09

1114

1228

1.24

1186

1303

1.40

1339

1343

1.60

1530

1600

1087

1.01

1001

1123

1.05

1073

1156

1.13

1150

1185

1.20

1226

1250

1.35

1291

1319

1.51

1444

1382

1.68

1607

1700

1114

1.07

1108

1151

1.15

1185

1183

1.23

1262

1215

1.31

1339

1276

1.48

1415

1334

1.64

1569

1398

1.80

1722

1800

1141

1.17

1221

1178

1.26

1318

1211

1.35

1390

1243

1.43

1461

1303

1.61

1540

1359

1.78

1702

1418

1.95

1865

1900

1168

1.28

1371

1204

1.37

1502

1238

1.47

1548

1271

1.56

1594

1330

1.74

1664

1386

1.93

1846

1439

2.11

2018

2000

1197

1.39

1485

1231

1.48

1604

1265

1.59

1666

1298

1.69

1727

1358

1.89

1808

1413

2.08

1989

1466

2.27

2171

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates field-supplied drive required. (See Note 4.)

2.

indicates field-supplied motor and drive required.

3.

indicates maximum usable bhp/watts.

4. Alternate motor drive range: 835 to 1185 rpm. All other rpms require a field-

supplied drive.

5. Values include losses for filters, unit casing, and wet coils.

6. Maximum continuous bhp is 1.00 and the maximum continuous watts are 1000.

Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance table on page 60 for additional information.

7. Use of a field-supplied motor may affect wire sizing. Contact your local repre-

sentative to verify.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.