Q-SERIES DI HEATER OPERATION / MAINTENANCE MANUAL

F1

F2

F3

F4

F5

Figure 5-2: Alarm Page

5.2.c Configuration Page

The Configuration page is used to change the method for communicating
to the heater and to select optimal PID settings for high flow or low flow
operating conditions.

Button F1 enables local operation (

) through the graphical user

interface or remote operation (

) through an external hardware

interface. When remote operation (

) is selected, the temperature

set point cannot be adjusted nor can the heating of water be enabled
or disabled locally through the display panel as described in section
5.2.a.

Button F2 enables the optimal preset PID configuration for High flow

(

) or Low flow (

) conditions. Refer to Table 5-1 when deciding

to select the Low flow (

) or High flow (

) configuration during

critical process steps.

„High Flow‟ PID Settings

„Low Flow‟ PID Settings

# Mod, Power

High Flow (GPM)

Low Flow (GPM)

High Flow (GPM)

Low Flow (GPM)

3, 36kW

1.6

0.5

0.6

0.1

6, 72kW

3.25

1.3

1.75

0.25

12, 120kW

5.4

2.1

3.0

0.5

12, 144kW

6.5

2.6

3.5

0.5

Table 5-1: Flow Settings

The following navigation buttons are also available for advancing to the
Home and Alarm pages: